CS-series B7A Interface Unit
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: November 12, 2012
| Item | Specifications | ||
|---|---|---|---|
| Transmission method | One-way time-sharing multiplex transmissions | ||
|
Transmission delay (communications delay on transmission path) |
High-speed | 3 ms typical, 5 ms max. | |
| Standard | 19.2 ms typical, 31 ms max. | ||
| Transmission points | CS1W-B7A12 | 32 inputs (2 ports) | |
| CS1W-B7A02 | 32 outputs (2 ports) | ||
| CS1W-B7A21 | 16 inputs (1 port), 16 outputs (1 port) | ||
| CS1W-B7A22 | 32 inputs (2 ports), 32 outputs (2 ports) | ||
|
External power supply voltage *1 |
12 to 24 V DC (allowable voltage range: 10.8 to 26.4 V) | ||
|
External supply current *2 |
CS1W-B7A12 | 20 mA min. | |
| CS1W-B7A02 | 60 mA min. | ||
| CS1W-B7A21 | 30 mA min. | ||
| CS1W-B7A22 | 60 mA min. | ||
|
Minimum input time *3 |
High-speed | 16 ms | |
| Standard | 2.4 ms | ||
| Transmission distance | High-speed | Power supply on one side (common power supply) |
10 m max. |
| 50 m max. (with shielded cable) | |||
| Power supply on both sides (separate power supplies) |
10 m max. | ||
| 100 m max. (with shielded cable) | |||
| Standard | Power supply on one side (common power supply) |
100 m max. | |
| Power supply on both sides (separate power supplies) |
500 m max. | ||
| Cables | VCTF, 0.75 mm2, 3 conductors (power supply on one side (common power supply)) VCTF, 0.75 mm2, 2 conductors (power supply on both sides (separate power supplies)) Shielded cable, 0.75 mm2, 3 conductors (power supply on one side (common power supply)) Shielded cable, 0.75 mm2, 2 conductors (power supply on both sides (separate power supplies)) |
||
| Model | CS1W-B7A12 | CS1W-B7A02 | CS1W-B7A21 | CS1W-B7A22 | |
|---|---|---|---|---|---|
| Applicable PLC | CS-series PLCs | ||||
| Unit type | CS1 Basic I/O Unit | ||||
|
I/O points |
Input | 32 inputs | --- | 16 inputs | 32 inputs |
| Output | --- | 32 outputs | 16 outputs | 32 outputs | |
|
Transmission distance |
Normal: 500m max. when the interface unit and the link terminal units have separate external power supplies, Normal: 100m max. when the interface unit and the link terminal units use a common external power supply, High speed: 100m max. with shielded cables, 10m max. with unshielded cables, when the interface unit and the link terminal units have separate external power supplies, High speed: 50m max. with shielded cables, 10m max. with unshielded cables, when the interface unit and the link terminal units use a common external power supply, |
||||
|
Transmission delay |
Normal: 19.2ms (typ.), 31ms max. Short 3ms (typ.), 5ms max. * 1 |
||||
| Weight | 230g max. | 240g max. | |||
|
Power supply voltage from external source *2 |
12 to 24VDC ±10%, 20mA min. |
12 to 24VDC ±10%, 60mA min. |
12 to 24VDC ±10%, 30mA min. |
12 to 24VDC ±10%, 60mA min. |
|
|
I/O memory allocation |
Each Unit is allocated 4 words in the I/O Area (which starts at CIO 0000). The words are allocated according to the mounting position of the Unit. |
||||
| 2 words (32 points). | 4 words (64 points). | ||||
|
Current consumption |
5 V DC: 90 mA max. (supplied from Power Supply Unit) | ||||
*1. The I/O delay time is selectable by the selector switch between normal and short.
*2. The value does not include the power supplied to B7A link terminal units.
last update: November 12, 2012