Motor Condition Monitoring Device
last update: April 1, 2022
Power
Supply |
Power supply voltage | K6CM-[][]MA: 100 to 240 VAC, 50/60 Hz
K6CM-[][]MD: 24 VAC, 50/60 Hz, 24 VDC |
|
---|---|---|---|
Allowable operating voltage range | 85% to 110% of power supply voltage | ||
Power supply frequency range | 45 to 65 Hz | ||
Power consumption | 24 VAC/24 VDC: 3.2 VA/1.7 W max.
100 to 240 VAC: 6.1 VA max. |
||
Input | Current,
comprehensive current diagnosis (CT) |
Rated input
current |
5 A, 25 A, 100 A, 200 A, 400 A, 600 A |
Applicable motor type | Three-phase induction motor (Rated voltage 600 VAC max) *1 | ||
Outputs | Output form | Transistor output | |
Output capacity | 3-point | ||
Output rating | Rated voltage: 24 VDC
Max. current: 50 mA, DC |
||
Ambient operating temperature | -10 to +55°C (with no condensation or icing) | ||
Storage temperature | -20 to +65°C (with no condensation or icing) | ||
Ambient operating humidity | 25% to 85% RH (with no condensation) | ||
Storage humidity | 25% to 85% RH (with no condensation) | ||
Case color | Black | ||
Case material | Polycarbonate UL94-V0 | ||
Altitude | 2,000 m max. | ||
Applicable wires | Stranded wires, solid wires, or ferrules | ||
Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to 16) | ||
Wire insertion force | 8 N max. (AWG20) | ||
Screwdriver insertion force | 15 N max. | ||
Wire stripping length | 8 mm | ||
Recommended flat-blade screwdriver | XW4Z-00B (Omron) | ||
Current capacity | 10 A (per pole) | ||
Number of insertions | 50 times | ||
Weight | Approx. 200 g | ||
Mounting | Mounts to DIN Track
screw mounting |
||
Dimensions | 45 (W) × 90 (H) × 90 (D) mm | ||
Setting method | Communications settings from a dedicated tool via EtherNet/IP | ||
Other functions | Display value selection, self-diagnosis error output, setting value
initialization, operation integration |
||
Accessories | Operation manual, CD-ROM (Motor condition monitoring Tool) |
Measurement range | Current
Rating 5 A: 1.00 to 5.00 A Rating 25 A: 5.0 to 25.0 A Rating 100 A: 20.0 to 100.0 A Rating 200 A: 40.0 to 200.0 A Rating 400 A: 80.0 to 400.0 A Rating 600 A: 120.0 to 600.0 A Rated frequency: 20 to 80 Hz Degradation level 1, degradation level 2: 0 to 999 Recommended frequency: 20 to 80 Hz *1 |
|
---|---|---|
Measurement
absolute accuracy |
Current | ±1.0% FS±1 digit (at 10 to 30°C, CT variation is not included) *2 |
Sampling cycle | Degradation level 1, degradation level 2, current: 5 s | |
Moving average frequency | 1, 2, 4, 8, 16, 32 times | |
External
trigger |
External contact input
specification |
Short-circuit: Residual voltage 1.5 V max.
Open: Leakage current 0.1 mA max. |
Current during short-
circuiting |
Approx. 7 mA | |
Transistor output | Contact configuration: NPN open collector
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC) Max. current: 50 mA, DC |
|
Alarm | Parameters that can be
output |
Degradation level 1, degradation level 2, current |
Expression method | Transistor output, alarm bar | |
Setting value | Current
Rating 5 A: 00.00 to 99.99 A Rating 25 A/100 A/ 200 A/400 A/600 A: 0.0 to 999.9 A Degradation level 1, degradation level 2: 0 to 9999 |
|
Hysteresis | 10% width of setting value | |
Reset method | Manual reset/automatic reset (switchable)
* Manual return method: Press the ALMRST button |
|
LCD display | 7-Segment digital display and single-shot display
Font height 14 mm |
|
Applicable
standards |
Conforming standards | EN61010-2-030
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
EMC | EN61326-1(EMI: Class A EMS: Industrial Location)
Current ± 10% F.S. |
|
Safety standards | UL61010-2-030 (listing) *5 / CSA 22.2 No.14 Overvoltage category II
Korean Radio Waves Act (Act 10564) RCM EAC |
|
Insulation resistance | 20 MΩ min.
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Dielectric strength | 2,000 VAC for 1 minute
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Vibration resistance | Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y,
Z directions 5 minute × 10 |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | IP20 | |
LED display | Alarm bar | Red/Yellow/Green |
MS, NS *3 | Red/Green | |
Ethernet
communications *4 |
Number of ports | 1 |
Physical layer | Ethernet: Connector RJ45 | |
Type | 100BASE-TX | |
Transmission distance
(Maximum cable length) |
100 m (Between hub and node) | |
Topology | Star type | |
Protocol | EtherNet/IP
Modbus TCP |
Model *3 | K6CM-
CICB005 |
K6CM-
CICB025 |
K6CM-
CICB100 |
K6CM-
CICB200 |
K6CM-
CICB400 |
K6CM-
CICB600 |
|
---|---|---|---|---|---|---|---|
Construction | Indoor split type | ||||||
Primary-side rated current | 5 A | 25 A | 100 A | 200 A | 400 A | 600 A | |
Measurement range *1 | 1 to 5 A | 5 to 25 A | 20 to 100 A | 40 to 200 A | 80 to 400 A | 120 to 600 A | |
Rated voltage | 600 VAC *4 | ||||||
Secondary-side rated current | Dedicated current | ||||||
Secondary winding | 3000 turns | 6000 turns | 9000 turns | ||||
Insulation resistance | Between output terminal and case: 50 MΩ min. | ||||||
Dielectric strength | Between output terminal and case: 2,000 VAC, 1 minute | ||||||
Protective element | 7.5 V clamp element | ||||||
Permissible attachment/removal
frequency |
100 times | ||||||
Attachable wire diameter *2 | 7.9 mm dia.
max. |
9.5 mm dia.
max. |
14.5 mm dia.
max. |
24.0 mm dia.
max. |
35.5 mm dia. max. | ||
Operating temperature/humidity
range |
-20 to +60°C, 25 to 85% (with no condensation or icing) | ||||||
Storage temperature/humidity
range |
-30 to +65°C, 25 to 85% (with no condensation or icing) | ||||||
Supplied cable length | 2.9 m (pre-wired cable) | ||||||
Supplied cable
terminal |
Main unit side | Ferrule terminal | |||||
CT side | Round terminal | ||||||
Degree of protection | IP20 |
Power
Supply |
Power supply voltage | K6CM-[][]MA: 100 to 240 VAC, 50/60 Hz
K6CM-[][]MD: 24 VAC, 50/60 Hz, 24 VDC |
|
---|---|---|---|
Allowable operating voltage range | 85% to 110% of power supply voltage | ||
Power supply frequency range | 45 to 65 Hz | ||
Power consumption | 24 VAC/24 VDC: 3.8 VA/2.1 W max.
100 to 240 VAC: 7.1 VA max. |
||
Input | Vibrations
(vibration sensor) |
Detection
frequency |
10 Hz to 10 kHz |
Max. operating
acceleration |
10 G | ||
Applicable motor type | Three-phase induction motor (Rated voltage 600 V or less) * | ||
Outputs | Output form | Transistor output | |
Output capacity | 3-point | ||
Output rating | Rated voltage: 24 VDC
Max. current: 50 mA, DC |
||
Ambient operating temperature | -10 to +55°C (with no condensation or icing) | ||
Storage temperature | -20 to +65°C (with no condensation or icing) | ||
Ambient operating humidity | 25% to 85% RH (with no condensation) | ||
Storage humidity | 25% to 85% RH (with no condensation) | ||
Case color | Black | ||
Case material | Polycarbonate UL94-V0 | ||
Altitude | 2,000 m max. | ||
Applicable wires | Stranded wires, solid wires, or ferrules | ||
Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to 16) | ||
Wire insertion force | 8 N max. (AWG20) | ||
Screwdriver insertion force | 15 N max. | ||
Wire stripping length | 8 mm | ||
Recommended flat-blade screwdriver | XW4Z-00B (Omron) | ||
Current capacity | 10 A (per pole) | ||
Number of insertions | 50 times | ||
Weight | Approx. 200 g | ||
Mounting | Mounts to DIN Track
screw mounting |
||
Dimensions | 45 (W) × 90 (H) × 90 (D) mm | ||
Setting method | Communications settings from a dedicated tool via EtherNet/IP | ||
Other functions | Display value selection, self-diagnosis error output, setting value
initialization, operation integration |
||
Accessories | Operation manual, CD-ROM (Motor condition monitoring Tool) |
Measurement range | Acceleration: 0.05 to 9.99 G, Velocity: 0.90 to 45.00 mm/s,
Motor temperature: 0 to 80°C, Differential temperature: 0 to 80°C |
|
---|---|---|
Measurement
absolute accuracy |
Acceleration | ±3 dB±2 digit (at 25°C) *5 |
Temperature | Motor temperature: ±3°C±2 digit (±6°F±2 digit) *1
Temperature Gap: ±6°C±2 digit (±12°F±2 digit) *1 |
|
Sampling cycle | Acceleration: 50 ms, Velocity: 0.5 s, Temperature: 0.5 s | |
Moving average frequency | 1, 2, 4, 8, 16, 32 times | |
External
trigger |
External contact input
specification |
Short-circuit: Residual voltage 1.5 V max.
Open: Leakage current 0.1 mA max. |
Current during short-
circuiting |
Approx. 7 mA | |
Transistor output | Contact configuration: NPN open collector
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC) Max. current: 50 mA, DC |
|
Alarm | Parameters that can
be output |
Degradation level, current |
Expression method | Transistor output, alarm bar | |
Setting value | Acceleration: 0.00 to 99.99 G, Velocity: 0.00 to 99.99 mm/s,
Motor temperature: 0 to 9999 deg., Differential temperature: 0 to 9999 deg. |
|
Hysteresis | 10% width of setting value | |
Reset method | Manual reset/automatic reset (switchable)
* Manual return method: Press the ALMRST button |
|
LCD display | 7-Segment digital display and single-shot display
Font height 14 mm |
|
Applicable
standards |
Conforming standards | EN61010-2-030
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
EMC | EN61326-1(EMI: Class A EMS: Industrial Location)
Acceleration ± 0.1G, Velocity ±2.25mm/s, Temperature ± 6°C |
|
Safety standards | UL61010-2-030 (listing)
Korean Radio Waves Act (Act 10564) RCM EAC |
|
Insulation resistance | 20 MΩ min.
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Dielectric strength | 2,000 VAC for 1 minute
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Vibration resistance | Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y,
Z directions 5 minute × 10 |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | IP20 | |
LED display | Alarm bar | Red/Yellow/Green |
MS, NS *2 | Red/Green | |
Ethernet
communications *3 |
Number of ports | 1 |
Physical layer | Ethernet: Connector RJ45 | |
Type | 100BASE-TX | |
Transmission distance
(Maximum cable length) |
100 m (Between hub and node) | |
Topology | Star type | |
Protocol | EtherNet/IP
Modbus TCP *4 |
Model | K6CM-VBS1 | |
---|---|---|
Power supply voltage | Supplied from K6CM-VB | |
Sensor head | Max. acceleration | 10 G |
Ambient operating temperature | Pre-amplifier: -10 to +55°C (with no condensation or icing)
Sensor head: -10 to +80°C (with no condensation or icing) |
|
Storage temperature | Pre-amplifier: -20 to +65°C (with no condensation or icing)
Sensor head: -20 to +90°C (with no condensation or icing) |
|
Ambient operating humidity | 25% to 85% RH (with no condensation) | |
Storage humidity | 25% to 85% RH (with no condensation) | |
Altitude | 2,000 m max. | |
Case color | Pre-amplifier: Black
Sensor head: Silver |
|
Case material | Pre-amplifier: Polycarbonate UL94-V0
Sensor head: Aluminum alloy (ADC12) / Zinc die casting (ZDC2) (the threaded part is Steel (S45C)) |
|
Weight | Pre-amplifier: Approx. 210 g (including cables)
Sensor head: Approx. 40 g (including cables) |
|
Mounting | Pre-amplifier: DIN rail mounting, screw mounting
Sensor head: Screw mounting Between pre-amplifier and sensor head: Connector connection (smart click connector) |
|
Wire length | Between pre-amplifier and sensor head: 2.6 m+0.3 m (cannot be extended)
Between pre-amplifier and main unit: 1 m Can be extended up to a maximum length of 100 m * |
* When extending the cable on the pre-amplifier side, use shielded twisted pair cable with wire gauges of AWG24 to 16.
Model | K6CM-VBS1 | |
---|---|---|
Measurement range | Specified in main unit “Characteristics” | |
Applicable
standards |
Conforming
standards |
EN 61010-2-030
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
EMC | EN 61326-1 (EMI: Class A EMS: Industrial Location) | |
Safety standards | UL 61010-2-030 (listing) *
RCM EAC |
|
Insulation resistance | 20 MΩ min. | |
Dielectric strength | 500 VAC for one minute | |
Vibration
resistance |
Pre-amplifier | Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y, Z directions
5 minute × 10 |
Sensor head | Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y, Z directions
5 minute × 10 |
|
Shock
resistance |
Pre-amplifier | 100 m/s2, 3 times each in 6 directions along 3 axes |
Sensor head | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of
protection |
Pre-amplifier | IP20 (excluding the sensor-side cable) |
Sensor head | Conforming to IP67G (JIS C 0920: 2003, Appendix 1) | |
LED display | Pre-amplifier PWR: Green, ERR: Red, COM: Orange |
* Except when K6CM-VBSAT1 or K6CM-VBSAT2 is used.
Power
Supply |
Power supply voltage | K6CM-[][]MA: 100 to 240 VAC, 50/60 Hz
K6CM-[][]MD: 24 VAC, 50/60 Hz, 24 VDC |
|
---|---|---|---|
Allowable operating voltage range | 85% to 110% of power supply voltage | ||
Power supply frequency range | 45 to 65 Hz | ||
Power consumption | 24 VAC/24 VDC: 3.7 VA/2.0 W max.
100 to 240 VAC: 6.2 VA max. |
||
Input | Insulation
resistance (ZCT (IRT)) |
Rated input
voltage |
(Line voltage) 200 to 480 VAC, 50 Hz/60 Hz |
Rated path
current |
300 AAC | ||
Applicable motor type | Three-phase induction motor (Rated voltage 480 V or less) * | ||
Outputs | Output form | Transistor output | |
Output capacity | 3-point | ||
Output rating | Rated voltage: 24 VDC
Max. current: 50 mA, DC |
||
Ambient operating temperature | -10 to +55°C (with no condensation or icing) | ||
Storage temperature | -20 to +65°C (with no condensation or icing) | ||
Ambient operating humidity | 25% to 85% RH (with no condensation) | ||
Storage humidity | 25% to 85% RH (with no condensation) | ||
Case color | Black | ||
Case material | Polycarbonate UL94-V0 | ||
Altitude | 2,000 m max. | ||
Applicable wires | Stranded wires, solid wires, or ferrules | ||
Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to 16) | ||
Wire insertion force | 8 N max. (AWG20) | ||
Screwdriver insertion force | 15 N max. | ||
Wire stripping length | 8 mm | ||
Recommended flat-blade screwdriver | XW4Z-00B (Omron) | ||
Current capacity | 10 A (per pole) | ||
Number of insertions | 50 times | ||
Weight | Approx. 200 g | ||
Mounting | Mounts to DIN Track
screw mounting |
||
Dimensions | 45 (W) × 90 (H) × 90 (D) mm | ||
Setting method | Communications settings from a dedicated tool via EtherNet/IP | ||
Other functions | Display value selection, self-diagnosis error output, setting value
initialization, operation integration |
||
Accessories | Operation manual, CD-ROM (Motor condition monitoring Tool) |
Measurement range | Insulation resistance: 0.000 M to 1.000 MΩ,
Leakage current: 0.0 mA to 200.0 mA |
|
---|---|---|
Measurement
absolute accuracy |
Insulation
resistance |
±35% rdg±2 digit (when the insulation resistance is 0.2 MΩ max.), when
a 200-V/7.5-kW max. motor is used *1 ±35% rdg±2 digit (when the insulation resistance is 0.4 MΩ max.), when a 400-V/7.5-kW max. motor is used *1 |
Sampling cycle | Normal mode: 10 s, Inverter special measurement mode: 60 s | |
Moving average frequency | 1, 2, 4, 8, 16, 32 times | |
External
trigger *2 |
External contact input
specification |
Short-circuit: Residual voltage 1.5 V max.
Open: Leakage current 0.1 mA max. |
Current during short-
circuiting |
Approx. 7 mA | |
Transistor output | Contact configuration: NPN open collector
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC) Max. current: 50 mA, DC |
|
Alarm | Parameters that can
be output |
Degradation level, current |
Expression method | Transistor output, alarm bar | |
Setting value | Insulation resistance: 0.000 M to 9.999 MΩ | |
Hysteresis | 10% width of setting value | |
Reset method | Manual reset/automatic reset (switchable)
* Manual return method: Press the ALMRST button |
|
LCD display | 7-Segment digital display and single-shot display
Font height 14 mm |
|
Applicable
standards |
Conforming standards | EN61010-2-030
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
EMC | EN61326-1(EMI: Class A EMS: Industrial Location)
Acceleration ± 0.1G, Velocity ±2.25mm/s, Temperature ± 6°C, insulation resistance ± 35% rdg |
|
Safety standards | UL61010-2-030 (listing)
Korean Radio Waves Act (Act 10564) RCM EAC |
|
Insulation resistance | 20 MΩ min.
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Dielectric strength | 2,000 VAC for 1 minute
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
|
Vibration resistance | Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y,
Z directions 5 minute × 10 |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | IP20 | |
LED display | Alarm bar | Red/Yellow/Green |
MS, NS *3 | Red/Green | |
Ethernet
communications *4 |
Number of ports | 1 |
Physical layer | Ethernet: Connector RJ45 | |
Type | 100BASE-TX | |
Transmission distance
(Maximum cable length) |
100 m (Between hub and node) | |
Topology | Star type | |
Protocol | EtherNet/IP
Modbus TCP *5 |
Model | K6CM-ISZBI52 | |
---|---|---|
Construction | Indoor split type | |
Rated path current | 300 A | |
Through hole dia. | 52 mm dia. | |
Rated voltage | 200 to 480 VAC, 50 Hz/60 Hz three phase | |
Measurement range | Specified in main unit “Characteristics” | |
Measurement accuracy | Specified in main unit “Characteristics” | |
Voltage input terminal | 3-terminal lead wire, Length: 1m (pre-wired cable) | |
Output terminal | 4-terminal lead wire, Length: 1m (pre-wired cable) Available wire length 100 m max. * | |
Applicable
standards |
Conforming
standards |
EN 61010-2-030
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
EMC | EN 61326-1 (EMI: Class A EMS: Industrial Location) | |
Safety standards | UL 61010-2-030 (Recognition) + CSA C22.2 No. 61010-2-030
RCM EAC |
|
Insulation resistance | Between Mounting bracket - Secondary winding: 100 MΩ min. | |
Dielectric strength | Between Mounting bracket - Secondary winding: 2000 VAC, 1 minute | |
Ambient operating temperature | -10 to +55°C (with no condensation or icing) | |
Ambient operating humidity | 25 to 85% (with no condensation) | |
Weight | Approx. 2.3 kg (including cables) | |
Degree of protection | IP20 |
* When extending the cable on the pre-amplifier side, use shielded twisted pair cable with wire gauges of AWG24 to 16.
Element | Specification |
---|---|
Supported OS | Windows 7, Windows 8.1, Windows 10 (32 bit/64 bit) (Japanese/English) |
.NET | .NET Framework 4 and .NET Framework 3.5 |
CPU | 1 GHz or more, 32 bit or 64 bit processor |
Memory | 1 GB or more, or 2 GB or more (for 64 bit) |
HDD | Available space of 16 GB or more, or 20 GB or more (for 64 bit) |
Others | Since this software is provided on a CD-ROM, a CD-ROM reading device must be available.
If data is to be collected, a LAN I/F must be available. |
(For more details, refer to the catalog of each product.)
Item | Specification | |
---|---|---|
Project | Number of files that can be created | No limit |
Log file | CSV data format | |
Monitoring cycle | 5 second to 366 days | |
Number that can be
registered in one project |
Number of motors (device groups) | 10 |
Number of devices per motor (device group) | 3 *1 | |
Graphic display | Type of graph | Line graph |
Display period *2 | 1 hour, 1 day, 1 month, 1 year |
last update: April 1, 2022