Page top

Industrial Automation

Industrial Automation

E8PC

IoT Pressure Sensors

E8PC

Detect signs of abnormalities in hydraulic oil and sealant by simultaneous measurement of “pressure + temperature”

Sensors

Model NPN/PNP selectable
(COM2)
E8PC-010SD-E E8PC-100SD-E E8PC-400SD-E
NPN/PNP selectable
(COM3)
E8PC-010ST-E E8PC-100ST-E E8PC-400ST-E
Pressure
monitoring
*1
Rated pressure range -0.1 to 1 MPa 0 to 10 MPa 0 to 40 MPa
Display range -0.20 to 1.10 MPa -0.10 to 11.00 MPa -0.10 to 44.00 MPa
Overload pressure *2 4 MPa 30 MPa 50 MPa
Burst pressure 8 MPa 60 MPa 80 MPa
Display resolution 0.001 MPa 0.01 MPa 0.01 MPa
Applicable fluid
temperature *3
-20 to +100°C (no icing or condensation)
Pressure response time
*4
Control output: Select 3 to 6000 ms
Analog output: Set value + 2 ms (90% response)
Pressure monitoring
precision
±1.0% of F.S. or less
Pressure repeatability *5 ±0.3% of F.S. or less
Ambient temperature
characteristics *6
±0.6% of F.S./10°C
Hysteresis Variable
Pressure type Gauge pressure
Temperature
monitoring
*7
Temperature monitoring
rated range
-20 to 100°C
Temperature monitoring
precision
±4°C
Temperature repeatability ±1°C
Control
output
judgment
(selectable)
Standard mode It is judged if the measured value is the threshold value or more (or
less).
Window mode It is judged if the measured value is within the upper and lower limits.
Compatible fluid Gas and fluid not
corroding the material
of the wetted part
(such as water, glycol
solution, and oil)
The fluid must not corrode the material of the
wetted part (e.g. water, water-soluble coolants,
insoluble oils)
Display method Numerical value indication: 4-digit 7-segment white LED with inverting
function
Status indicator: The content of indication is selectable from green,
orange, red, and OFF.
Output indicator: OUT1 operation (orange), OUT2 operation (orange)
Unit indication:
E8PC-[][][]S[]: MPa (white), °C (white)
E8PC-[][][]S[]-E: MPa (white), bar (white), psi (white), °C (white)
Communication indicator: IO-Link mark (green)
Delay setting 1 to 9999 ms
(Select a function from invalid, ON delay, OFF delay, and one-shot.)
Connection method M12, 4-pole connector type
Connecting diameter G3/4 male (Use the optional adapter to convert the diameter) Connection
strength 20 N·m
Output ch1 Control output Pressure control output (N.O./N.C.) /temperature control output (N.O./
N.C.)
NPN/PNP selectable
30 VDC or less, max. 100 mA/ch, residual voltage 1 V or less
Analog current output *8 Pressure analog output / Temperature analog output
Current output 4 to 20 mA (maximum load resistance 350Ω or less)
(Display value ± 2% of F.S.)
Output ch2 Control output Pressure control output (N.O./N.C.) / Temperature control output (N.O./
N.C.)
NPN/PNP selectable
30 VDC or less, max. 100 mA/ch, residual voltage 1 V or less
Analog current output *8 Pressure analog output / Temperature analog output
Current output 4 to 20 mA (maximum load resistance 350Ω or less)
(Display value ± 2% of F.S.)
External input One-point teaching/zero point adjustment input (selectable, initial status:
invalid)
short-circuit current 1.5 mA or less, input time 20 ms or more
IO-Link IO-Link specification Ver 1.1
Baud rate E8PC-[][][]SD-[]: COM2 (38.4kbps)
E8PC-[][][]ST-[]: COM3 (230.4Kbps)
Data length PD Size: 6 byte
OD Size: 1 byte (M-sequence type: TYPE_2_V)
Minimum cycle time E8PC-[][][]SD-[] (COM2): 3.2 ms
E8PC-[][][]ST-[] (COM3): 2.0 ms
Power
supply
Power supply voltage 10 to 30 VDC (including 10% ripple (p-p)), Class 2
Power consumption 1,200 mW or less
(When power supply voltage is 30 V, current consumption must be 40
mA or less.
When power supply voltage is 10 V, current consumption must be 120
mA or less.)
Protection circuit Power supply reverse connection protection, output short-circuit
protection, and output reverse connection protection
Environment
resistance
Ambient temperature
range
-20 to 70°C in operation and storage, respectively (no condensation)
Ambient humidity range -35 to 85%RH in operation and storage, respectively (no condensation)
Vibration resistance
(destruction)
1000 VAC, 50/60 Hz, 1 min. between current-carrying parts and case
Shock resistance
(destruction)
10 to 2000 Hz, double amplitude 1.5 mm, 2 hours in X/Y/Z direction each
Impact (endurance) 500 m/s2, three times in X/Y/Z direction each
Protective structure IP67
Material Wetted part Pressure port: SUS304, diaphragm pressure port: Al2O3 (alumina),
O-ring: FKM
Other than wetted part Head: PPSU, display unit: PES, button: PBT, chassis: SUS304L
Weight Approx.190 g
Accessories • Throttle (Model E8PC-YS and E8PC-YS-N), one each
• O-ring x 1 (Model E8PC-010S[]-[]: Model E8PC-YL-1,
Model E8PC-100S[]-[]/E8PC-400S[]-[]: Model E8PC-YL-2)
• User's manual (Japanese, English, and Chinese), one each
• Compliance sheet
• Index list

*1. The pressure precision is defined based on the values measured in the ordinary temperature environment (approx. 23°C)
      using water at the ordinary temperature (approx. 23°C).
*2. Even instantaneous pressure fluctuation such as water hammer must be within the withstand pressure.
      If instantaneous pressure fluctuation is expected, use the throttle included in the package.
*3. If the pipe temperature exceeds 70°C, do not contact any cables with the pipe.
*4. The maximum actual response time has error of 1 ms when the set response time is 3 to 10 ms, 5 ms when it is
      11 to 100 ms, and +5% when it is 101 ms or more.
*5. The pressure repeatability is the error of the detection point when pressure is applied repeatedly in the ordinary
      temperature environment (approx. 23°C) using water at the ordinary temperature (approx. 23°C) in the rated pressure
      range.
*6. The ambient temperature characteristics are prescribed based on the value measured using oil as applying a pressure
      value of 50% of the maximum rated pressure.
*7. The temperature monitoring precision is prescribed based on the value measured using water.
      Temperature measurements are affected by both of the temperatures, the medium and the piping.
      Temperature measuring elements are installed on the back surface of the piezoelectric element (inside the product) and
      used to measure the temperature. It might take long for the measured value to get stable according to the heat
      transmission speed.
*8. Do not connect CH1 (pin4) or/and CH 2 (pin 2) with the IO-Link master unit in analog current output mode. Otherwise,
      the unit might fail.