Water Leak Detector
last update: August 26, 2019
Item | Water Leak Detector |
---|---|
Model | 61F-GPN-V50 |
Supply voltage | 24, 110, 120, 220, 230, 240 VAC |
Operating voltage range | 85% to 110% of rated voltage |
Interelectrode voltage | 24 VAC |
Operating current | 3 mA (AC) max. |
Power consumption | 3.2 VA max. |
Sensitivity | Variable (0 to 50 kΩ) |
Sensitivity error | Scale 0: 0 to 10 kΩ *
Scale 50: 50 ±10 kΩ |
Contact ratings | 3 A 250 VAC, DPDT cosφ=1
1 A 250 VAC, DPDT cosφ=0.4 |
Indicator | Provided (Operation indicator) |
Alarm buzzer | Not provided |
Test switch | Not provided |
Ambient temperature | -10 to 50°C |
Ambient humidity | 45% to 85% |
Accessories | Hold-down clip PFC-N8 |
Approved standards | UL508
CSA C22.2 No.14 EN61010-1 EN61326-1 Industrial electromagnetic environment |
* The Detector may not operate around the setting value of “0.” Adjust the sensitivity depending on the actual application.
last update: August 26, 2019