* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: October 1, 2020
Item | Single operation | Parallel operation | ||
---|---|---|---|---|
Efficiency (TYP.) | 24-V models: 80% TYP. ; 12-V models: 73% TYP. (with rated input, 100% load) | |||
Input | Voltage *1 | Ratings: 100 to 240 VAC (Allowable range: 85 to 264 VAC, 80 to 370 VDC *8) | ||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||
Current | 100 V input | 24-V models: 1.0 A max.
12-V models: 0.7 A max. |
24-V models: 1.0 A × (No. of Blocks) max.
12-V models: 0.7 A × (No. of Blocks) max. |
|
200 V input | 24-V models: 0.5 A max.
12-V models: 0.4 A max. |
24-V models: 0.5 A × (No. of Blocks) max.
12-V models: 0.4 A × (No. of Blocks) max. |
||
Power factor | 24-V models: 0.9 min.; 12-V models: 0.8 min. (with rated input, 100% load) | |||
Harmonic current
emissions |
Conforms to EN61000-3-2 | |||
Leakage
current |
100 V input | 0.35 mA max. | 0.35 mA × (No. of Blocks) max. | |
240 V input | 0.7 mA max. | 0.7 mA × (No. of Blocks) max. | ||
Inrush
current *5 |
100 V input | 17.5 A max. (for a cold start at 25°C) | 17.5 A × (No. of Blocks) max. (for a cold
start at 25°C) |
|
200 V input | 35 A max. (for a cold start at 25°C) | 35 A × (No. of Blocks) max. (for a cold
start at 25°C) |
||
Output
*4 |
Voltage adjustment
range |
24-V models: 22 to 28 V
12-V models: 12 V ±10% (with V.ADJ) *2 |
||
Ripple | 2% (p-p) max. | |||
Input variation
influence |
0.5% max. (with 85 to 264 VAC input, 100% load) | |||
Load variation
influence |
2% max. (with rated input, 10% to
100% load) |
3% max. (with rated input, 10% to 100% load) | ||
Temperature variation
influence |
0.05%/°C max. (with rated input and output) | |||
Startup time | 1,000 ms max. (with 100/200 VAC, rated input) | |||
Hold time *5 | 20 ms min. (with 100/200 VAC, rated input) | |||
Addi-
tional func- tions |
Overload protection
*5 |
105% to 140% of rated load current,
voltage drop, automatic reset |
100% to 140% of rated load current, voltage
drop, automatic reset |
|
Overvoltage
protection *5 *6 |
Yes | |||
Parallel operation | Yes (Up to 4 Blocks) | |||
N+1 redundant
system |
Yes (Up to 5 Blocks) | |||
Series operation | Yes | |||
Undervoltage
indicator *5 |
Yes (color: red) | |||
Undervoltage
detection output *5 |
Yes (open collector output), 30 VDC max., 50 mA max. | |||
Other | Ambient operating
temperature *5 |
Refer to the derating curve in Engineering Data on Data Sheet (with no icing or
condensation). |
||
Storage temperature | -25 to 65°C | |||
Ambient operating
humidity |
25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 minute (between all inputs and all outputs; detection current: 20 mA) | |||
2.0 kVAC for 1 minute (between all inputs and PE terminal; detection current: 20 mA) | ||||
1.0 kVAC for 1 minute (between all outputs and PE terminal; detection current: 20
mA) |
||||
Insulation resistance | 100 MΩ min. (between all outputs, and all inputs/PE terminal) at 500 VDC | |||
Vibration resistance
*7 |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions | |||
Shock resistance *7 | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | |||
Output indicator | Yes (color: green) | |||
EMI *8 | Conducted
Emission |
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A *9 | ||
Radiated
Emission |
Conforms to EN61204-3 EN55011 Class B *9 | |||
EMS *8 | Conforms to EN61204-3 High severity levels *9 | |||
Approved standards
*8 |
24V model
UL Listed: UL508 (Listing, Class2 Output: Per UL1310) (See note 3.) cUL Listed: CSA C22.2 No.107.1 (Class2 Output: Per CSA C22.2 No.223) (See note 3.) EN: EN62477-1 12V model UL Listed: UL508 (Listing) cUL Listed: CSA C22.2 No.107.1 EN: EN62477-1 |
|||
Weight | 450 g max. | 450 g × (No. of Blocks) max. |
Item | Single operation | ||
---|---|---|---|
Efficiency (typical) | 73% TYP. (with rated input, 100% load) | ||
Input | Voltage *1 | Ratings: 100 to 240 VAC (Allowable range: 85 to 264 VAC, 80 to 370 VDC *7) | |
Frequency *1 | 50/60 Hz (47 to 63 Hz) | ||
Current | 100 V input | 0.7 A max. | |
200 V input | 0.4 A max. | ||
Power factor | 0.8 min. (with rated input, 100% load) | ||
Harmonic current emissions | Conforms to EN61000-3-2 | ||
Leakage
current |
100 V input | 0.35 mA max. | |
240 V input | 0.7 mA max. | ||
Inrush
current *5 |
100 V input | 17.5 A max. (for a cold start at 25°C) | |
200 V input | 35 A max. (for a cold start at 25°C) | ||
Output
*3 |
Voltage adjustment range | 5 V ± 10% (with V. ADJ) *2 | |
Ripple | 2% (p-p) max. | ||
Input variation influence | 0.5% max. (with 85 to 264 VAC input, 100% load) | ||
Temperature variation
influence |
0.05%/°C max. (with rated input and output) | ||
Load variation influence | 1.5% max. (with rated input, 10% to 100% load) | ||
Startup time *4 | 1,000 ms max. (with 100/200 VAC, rated input) | ||
Hold time *4 | 20 ms min. (with 100/200 VAC, rated input) | ||
Addi-
tional func- tions |
Overload protection *4 | 105% to 140% of rated load current, voltage drop, automatic reset | |
Overvoltage protection
*4 *5 |
Yes | ||
Parallel operation | No | ||
N+1 redundant system | No | ||
Series operation | Yes (with the external diode) | ||
Undervoltage indicator *4 | Yes (color: red) | ||
Undervoltage detection
output *4 |
Yes (open collector output), 30 VDC max., 50 mA max. | ||
Other | Ambient operating
temperature *4 |
Refer to the derating curve in Engineering Data on Data Sheet. | |
Storage temperature | -25 to 65°C (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85%, Storage: 25% to 90% | ||
Dielectric strength | 3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection
current: 20 mA) |
||
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and PE terminal; detection
current: 20 mA) |
|||
1.0 kVAC for 1 minute (between all outputs and PE terminal; detection current:
20 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and inputs/PE terminal) at 500 VDC | ||
Vibration resistance *6 | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions | ||
Shock resistance *6 | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | ||
Output indicator | Yes (color: green) | ||
EMI *7 | Conducted
Emission |
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A | |
Radiated
Emission |
Conforms to EN61204-3 EN55011 Class B | ||
EMS *7 | Conforms to EN61204-3 High severity levels | ||
Approved standards *7 | UL Listed: UL508 (Listing)
UL UR: UL60950-1 (Recognition) cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No.60950-1 EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil1) |
||
Weight | 450 g max. |
last update: October 1, 2020