Solid State Relays
last update: May 20, 2024
Model | Rated voltage | Operating voltage |
Input current |
Voltage level | |
---|---|---|---|---|---|
Must operate voltage |
Must release voltage |
||||
G3TA-IAZR02S-US | 100 to 240 VAC | 80 to 264 VAC | 5 mA max. | 80 VAC max. | 10 VAC min. |
G3TA-IDZR02S-US | 5 to 24 VDC | 4 to 32 VDC | 4 VDC max. | 1 VDC min. | |
G3TA-IDZR02SM-US | 4 to 24 VDC | 3 to 32 VDC | 3 VDC max. |
Model |
Logic level supply voltage |
Output breakdown voltage |
Output current |
Output current (load current) |
VCEO (reference value) |
---|---|---|---|---|---|
G3TA-IAZR02S-US | 4 to 32 VDC | 32 VDC max. | 25 mA max. | 0.1 to 25 mA | 80 V |
G3TA-IDZR02S-US | |||||
G3TA-IDZR02SM-US |
Model |
Rated voltage |
Operating voltage |
Input impedance |
Voltage level | |
---|---|---|---|---|---|
Must operate voltage |
Must release voltage |
||||
G3TA-OA202SZ-US | 12 VDC | 9.6 to 13.2 VDC | 0.9 kΩ±20% | 9.6 VDC max. | 2 VDC min. |
24 VDC | 19.2 to 26.4 VDC | 1.7 kΩ±20% | 19.2 VDC max. | ||
G3TA-OA202SL-US | 12 VDC | 9.6 to 13.2 VDC | 0.9 kΩ±20% | 9.6 VDC max. | |
24 VDC | 19.2 to 26.4 VDC | 1.7 kΩ±20% | 19.2 VDC max. | ||
G3TA-ODX02S-US | 12 VDC | 9.6 to 13.2 VDC | 3.5 kΩ±20% | 9.6 VDC max. | |
24 VDC | 19.2 to 26.4 VDC | 6.5 kΩ±20% | 19.2 VDC max. | ||
G3TA-OD201S-US | 12 VDC | 9.6 to 13.2 VDC | 3.6 kΩ±20% | 9.6 VDC max. | |
24 VDC | 19.2 to 26.4 VDC | 6.4 kΩ±20% | 19.2 VDC max. |
Model |
Rated load voltage |
Load voltage range |
Load current (See note.) |
Inrush current |
VDRM, VCEO (reference value) |
---|---|---|---|---|---|
G3TA-OA202SZ-US | 100 to 240 VAC | 75 to 264 VAC | 0.05 to 2 A | 30 A (60 Hz, 1 cycle) | 600 (VDRM) |
G3TA-OA202SL-US | 100 to 240 VAC | 75 to 264 VAC | |||
G3TA-ODX02S-US | 5 to 48 VDC | 4 to 60 VDC | 0.01 to 2 A | 12 A (10 ms) | 80 (VCEO) |
G3TA-OD201S-US | 48 to 200 VDC | 40 to 200 VDC | 0.01 to 1 A | 6 A (10 ms) | 400 (VCEO) |
Note: The minimum current value is measured at 10°C min.
Item | G3TA-IAZR02S-US | G3TA-IDZR02S-US | G3TA-IDZR02SM-US |
---|---|---|---|
Operate time | 20 ms max. | 0.5 ms max. | |
Release time | 20 ms max. | 0.5 ms max. | |
Output ON voltage drop | 1.6 V rms max. | 1.6 V max. | |
Leakage current | 5 μA max. | ||
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength | 4,000 VAC, 50/60 Hz for 1 min between input and output | ||
Vibration resistance | Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude | ||
Shock resistance | Malfunction: 1,000 m/s2 | ||
Ambient temperature | Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation) |
||
Ambient humidity | Operating: 45% to 85% | ||
Certified standards | UL508 file No. E64562/CSA C22.2 (No. 0, No. 14) file No. LR35535 | ||
Weight | Approx. 16 g | ||
MTTFd (Reference value) | 1,000 years min. |
Certified standards | G3TA-OA202SZ-US | G3TA-OA202SL-US | G3TA-ODX02S-US | G3TA-OD201S-US |
---|---|---|---|---|
Operate time | 1/2 of load power source
cycle + 1 ms max. |
1 ms max. | 0.5 ms max. | 2 ms max. |
Release time | 1/2 of load power source
cycle + 1 ms max. |
2 ms max. | 2 ms max. | |
Output ON
voltage drop |
1.6 V rms max. | 1.6 V max. | 2.5 V max. | |
Leakage
current |
5 mA max. (at 200 VAC) | 1 mA max. | ||
Insulation
resistance |
100 MΩ min. (at 500 VDC) | |||
Dielectric
strength |
4,000 VAC, 50/60 Hz for 1 min between input and output | |||
Vibration
resistance |
Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude | |||
Shock
resistance |
Malfunction: 1,000 m/s2 | |||
Ambient
temperature |
Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation) |
|||
Ambient humidity | Operating: 45% to 85% | |||
Certified standards | UL508 file No. E64562, CSA C22.2 (No. 14) file No. LR3553 | |||
Weight | Approx. 23 g | |||
MTTFd
(Reference value) |
1,000 years min. |
With up to four G3TA SSRs mounted before G7T Relays, switching is possible at the rated load current for each Relay.
With G3TA SSRs mounted before every other G7T Relays, switching is possible at the rated load current for each Relay.
last update: May 20, 2024