H3DKZ

22.5-mm-width Timers

H3DKZ

Range of DIN Track-mounted, Standard 22.5-mm-width Timers

ON-delay Timer
H3DKZ-A

Time Ranges

Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to
120 min
1 to 12 h 10 to 120 h 100 to
1,200 h
Scale numbers 12

Ratings

Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage *3
Power consumption *4 H3DKZ-A1 At 240 VAC: 6.6 VA max.
H3DKZ-A2 At 240 VAC: 4.5 VA max.
Control output Contact output, 5 A at 250 VAC with resistive load (cosφ = 1), 5 A at 30 VDC
with resistive load
Ambient operating temperature -20 to 55°C (with no icing)
Storage temperature -40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%

*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this
       inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such as
       a sensor.
*2. DC ripple: 20% max.
*3. Actual value
*4. The power consumption is for mode A after the Timer times out.
*5. Refer to DC Power Consumptions (Reference Information) on Data sheet for DC power consumptions.

Characteristics

Accuracy of operating time ±1% of FS max.
Setting error ±5% of FS *
Influence of voltage ±2% of FS max. *
Influence of temperature ±5% of FS max. *
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
Between contacts of different polarity: 2,000 VAC 50/60 Hz for 1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life
expectancy
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
EMC (EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line, 1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g

* Actual value.

Twin Timer
H3DKZ-F

Time Ranges

Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to
120 min
1 to 12 h 10 to 120 h 100 to
1,200 h
Scale numbers 12

Ratings

Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage *3
Power consumption H3DKZ-F At 240 VAC: 4.5VA max. *4
H3DKZ-FA At 12 VDC: 0.6 W max.
Control output Contact output (SPDT): 5 A at 250 VAC with resistive load (cosφ = 1), 5 A at
24 VDC with resistive load *3, *4
Ambient operating temperature -20 to 55°C (with no icing)
Storage temperature -40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%

*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this
       inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such as
       a sensor.
*2. DC ripple: 20% max.
*3. Actual value.
*4. Refer to DC Power Consumptions (Reference Information) on Data Sheet for DC power consumptions.

Characteristics

Accuracy of operating time ±1% of FS max.
Setting error ±5% of FS ±0.05 s max. *
Influence of voltage ±2% of FS max. *
Influence of temperature ±5% of FS max. *
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Vibration
resistance
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life
expectancy
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
EMC (EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line, 1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 110 g

* Actual value.

Star-delta Timer
H3DKZ-G

Time Ranges

Time range setting t1x1 t1x10
Star set time (t1) range 1 to 12 s 10 to 120 s

Star-Delta transfer time (t2) Select from 0.05, 0.1, 0.25, or 0.5 s.

Ratings

H3DKZ-G H3DKZ-GE
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2 240 to 440 VAC (50/60 Hz)
Allowable voltage fluctuation
range
24 to 240 VAC/DC: 85% to 110% of rated voltage
240 to 440 VAC: 80% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.5 s
Reset voltage 10% of rated voltage *3
Power consumption At 240 VAC: 6.6 VA max. *4 At 440 VAC: 34 VA max.
Control output Contact output (Time-limit output: relay, Star
output: SPDT, Delta output: SPDT):
5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 24 VDC with resistive load *4, *5
I th 2 A
AC-15 120 VAC: 1.5 A
AC-15 240 VAC: 1 A
AC-15 440 VAC: 0.3 A
Ambient operating temperature -20 to 55°C (with no icing)
Storage temperature -40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%

*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this
       inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such as
       a sensor.
*2. DC ripple: 20% max.
*3. Actual value.
*4. Refer to DC Power Consumptions (Reference Information) on Data Sheet for DC power consumptions.
*5. 125 VDC: 0.15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
        Minimum load: 10 mA at 5 VDC (P level, reference value)

Characteristics

H3DKZ-G H3DKZ-GE
Accuracy of operating time ±1% of FS max.
Setting error ±5% of FS ±0.05 s max. *1
Transfer time Total error ± (25% of transfer time + 5 ms) max. *1
Influence of voltage ±2% of FS max. *1
Influence of temperature ±5% of FS max. *1
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC 50/60 Hz for 1 min. *2
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min. *2
Between contacts of different polarity: 2,000 VAC 50/60 Hz for 1 min. *2
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Vibration
resistance
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life
expectancy
Mechanical 10 million operations min. (under no load
at 1,800 operations/h)
10 million operations min. (under no load
at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC,
resistive load at 360 operations/h)
100,000 operations min. (0.3 A at 440 VAC,
resistive load at 1,800 operations/h)
EMC (EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line, 1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g

*1. Actual value.
*2. The dielectric strength of the H3DKZ-GE (240 to 440 VAC) is 2,500 VAC 50/60 Hz.

Power OFF-delay Timer
H3DKZ-H

Time Ranges

L Series
Time range setting x1 x10
Set time range 1 to 12 s 10 to 120 s
Power ON time 0.3 s min.
Scale numbers 12

Ratings

Supply voltage 100 to 120 VAC, 50/60 Hz
200 to 240 VAC, 50/60 Hz
Allowable voltage fluctuation range 85% to 110% of rated voltage
Power consumption H3DKZ-HCL At 120 VAC: 11.7 VA max.
H3DKZ-HDL At 240 VAC: 29.5 VA max.
Control output Contact output, 5 A at 250 VAC with resistive load (cosφ = 1), 5 A at 30 VDC
with resistive load
Ambient operating temperature -20 to 55°C (with no icing)
Storage temperature -40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%

* The control output ratings are for one H3DKZ operating alone.

Characteristics

Accuracy of operating time ±1% of FS max.
Setting error ±5% of FS *
Influence of voltage ±2% of FS max. *
Influence of temperature ±5% of FS max. (±2% ±10 ms max. at 1.2-s range) *
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Vibration
resistance
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life
expectancy
Mechanical 10 million operations min. (under no load at 1,200 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
EMC (EMI) EN 61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN 61000-3-3
(EMS) EN 61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line, 1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g

* Actual value.